Logo  
 中文    

   

  • Home
  • R718B-Wireless Resistance Temperature Detector

Image

Click on above image to view full picture

R718B-Wireless Resistance Temperature Detector

   

R718B connects an external resistance temperature detector (PT1000) to measures the temperature.

Be the first to review this product

R718B connects an external resistance temperature detector (PT1000) to measures the temperature.

• Adopt SX1276 LoRa wireless communication module
• 2 ER14505 battery AA SIZE (3.6V / section) parallel power supply
• PT1000 Platinum resistance temperature sensor detection
• The base is attached with a magnet that can be attached to a ferromagnetic material object
• Protection class IP65 / IP67 (optional)
• Compatible with LoRaWANTM Class A
• Frequency hopping spread spectrum
• Configuration parameters can be configured via a third-party software platform, data can be read and alerts can be set via SMS text and email (optional)
• Applicable to third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne
• Low power consumption and long battery life
Note:
Battery life is determined by the sensor reporting frequency and other variables, please refer to http://www.netvox.com.tw/electric/electric_calc.html
On this website, users can find battery life of various models in different configurations.

Electric:

Input Power

2 x 3.6V ER14505 AA size lithium batteries

Operating Voltage Range

3.1v - 3.65v

Standby Current

23uA

Wakeup Current

9.94mA (Typical value)
Wakeup current range 0.8mA-20 mA0.8mA-20mA
* When not transmitting /receiving LoRa data

Receiving Current (max)

11mA@3.3V

Transmitting Current (max)

120mA/3.3V

Battery Voltage Measurement Accuracy

±0.1V

Low Voltage Threshold

3.2V

Temperature Measurement Range

-40 to 200°C

Temperature Measurement Accuracy

The host body and the external PT1000 are in the same temperature range:
Temperature Range: 0℃ ≤ t ≤ 55℃, Accuracy: ±0.5℃

The host body and the external PT1000 are in different temperature ranges:
Temperature Range T1: 0℃ ≤ T1 ≤ 55℃ (Host body)
Temperature Range T2: -40℃ ≤ T2 < 0℃ (PT1000)
Accuracy: ±{(0.15 + 0.002*|T2|)+1}℃

Temperature Range T1: 0℃ ≤ T1 ≤ 55℃ (Host body)
Temperature Range T2: 55℃ < T2 ≤ 200℃ (PT1000)
Accuracy: ±{(0.15 + 0.002*|T2|)+0.3}℃
* t, T1, T2 refers to temperature

Lead Length

2m (default)

Probe Specifications

1: Probe diameter 5mm, needle probe 15cm (316 stainless steel)
2: Probe diameter 5mm, round head probe 30mm (316 stainless steel)
3: Probe diameter 5mm* length 100+60mm L-type probe (316 stainless steel)
Choose one of the above probe specifications.


Frequency:

Frequency Range

863MHz-928MHz 470MHz-510MHz

TX Power

US915 20dbm;
AS923 16dbm;
AU915 20dbm;
CN470 19.15dbm;
EU868 16dbm;
KR920 14dbm;
IN865 20dbm;

Receiving Sensitivity

-136dBm(LoRa,Spreading Factor=12,Bit Rate=293bps );
-121dBm (FSK,Frequency deviation=5kHz, Bit Rate=1.2kbps)

Antenna Type

Built-in antenna

Communication Distance

Up to 10 km
(visible linear obstacle-free transmission distance , actual transmission distance depends on the environment )

Data Transfer Rate

LoRa: 0.3kbps~50kbps
FSK: 1.2kbps~300kbps

Modulation

LoRa/FSK (Note: You can choose one of them)

Supportable LoRaWAN Band

EU863-870,US902-928,AU915-928,KR920-923,AS923-1,AS923-2,AS923-3,
IN865-867,CN470-510

(Note: The frequency band is optional and needs to be configured before shipment)


Physical:

Dimension

Main Part: L: 112mm*W: 88.19mm*H: 32mm

Weight

141g

Environment Temperature Range

-20℃ ~ 55℃

Environment Humidity Range

<90% RH (No condensation)